range of product | Easy Altivar 610 |
---|---|
Product or component type | Variable speed drive |
Product specific application | Fan, pump, compressor, conveyor |
Device short name | ATV610 |
variant | Standard version |
Product destination | Asynchronous motors Synchronous motors |
Mounting mode | Cabinet mount |
EMC filter | Integrated conforming to IEC 61800-3 category C3 with 50 m |
IP degree of protection | IP20 |
Type of cooling | Forced convection |
Supply frequency | 50...60 Hz +/-5 % |
Network number of phases | 3 phases |
[Us] rated supply voltage | 380...460 V - 15...10 % |
Motor power kW | 11 kW for normal duty 7.5 kW for heavy duty |
Motor power hp | 15 hp for normal duty 10 hp for heavy duty |
Line current | 22 A at 380 V (normal duty) 19.6 A at 460 V (normal duty) 16.4 A at 380 V (heavy duty) 14.6 A at 460 V (heavy duty) |
Prospective line Isc | 22 kA |
Apparent power | 15.6 kVA at 460 V (normal duty) 11.6 kVA at 460 V (heavy duty) |
Continuous output current | 23.5 A at 4 kHz for normal duty 16.5 A at 4 kHz for heavy duty |
Maximum transient current | 25.9 A during 60 s (normal duty) 24.8 A during 60 s (heavy duty) |
Asynchronous motor control profile | Constant torque standard Optimized torque mode Variable torque standard |
Output frequency | 0.1…500 Hz |
Nominal switching frequency | 4 kHz |
Switching frequency | 2...12 kHz adjustable |
number of preset speeds | 16 preset speeds |
communication port protocol | Modbus serial |
Option card | Slot A: communication card, Profibus DP V1 Slot A: digital or analog I/O extension card Slot A: relay output card |
Output voltage | <= power supply voltage |
---|---|
Motor slip compensation | Automatic whatever the load Adjustable Not available in permanent magnet motor law Can be suppressed |
Acceleration and deceleration ramps | S, U or customized Linear adjustable separately from 0.01 to 9000 s |
Braking to standstill | By DC injection |
Protection type | Thermal protection: motor Motor phase break: motor Thermal protection: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive |
Frequency resolution | Display unit: 0.1 Hz Analog input: 0.012/50 Hz |
Electrical connection | Control, screw terminal: 0.5...1.5 mm² Line side, screw terminal: 4...16 mm² Motor, screw terminal: 4...16 mm² |
Connector type | 1 RJ45 (on the remote graphic terminal) for Modbus serial |
Physical interface | 2-wire RS 485 for Modbus serial |
Transmission frame | RTU for Modbus serial |
Transmission rate | 4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial |
Type of polarization | No impedance for Modbus serial |
Number of addresses | 1…247 for Modbus serial |
Method of access | Slave |
Supply | External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection |
Local signalling | 2 LEDs for local diagnostic 1 LED (yellow) for embedded communication status 2 LEDs (dual colour) for communication module status 1 LED (red) for presence of voltage |
Width | 171 mm |
Height | 360 mm 423 mm with EMC plate |
Depth | 233 mm |
Net weight | 7.730 kg |
analogue input number | 3 |
Analogue input type | AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 30 kOhm, resolution 12 bits AI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits AI2, AI3 software-configurable temperature probe or water level sensor |
Discrete input number | 6 |
Discrete input type | DI1...DI6 programmable as logic input, 24 V DC (<= 30 V), impedance: 3.5 kOhm DI5, DI6 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V) |
Input compatibility | DI1...DI6: logic input level 1 PLC conforming to IEC 61131-2 DI5, DI6: pulse input level 1 PLC conforming to IEC 65A-68 |
Discrete input logic | Positive logic (source): DI1...DI6 configurable logic input, < 5 V (state 0), > 11 V (state 1) Negative logic (sink): DI1...DI6 configurable logic input, > 16 V (state 0), < 10 V (state 1) Positive logic (source): DI5, DI6 configurable pulse input, < 0.6 V (state 0), > 2.5 V (state 1) |
analogue output number | 2 |
Analogue output type | Software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits Software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits |
Sampling duration | 5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input 2 ms +/- 0.5 ms (DI1...DI6)configurable - discrete input 5 ms +/- 1 ms (DI5, DI6)configurable - pulse input 10 ms +/- 1 ms (AQ1, AQ2) - analog output |
Accuracy | +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output |
Linearity error | AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input AQ1, AQ2: +/- 0.2 % for analog output |
Relay output number | 3 |
Relay output type | Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles |
Refresh time | Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms) |
Minimum switching current | Relay output R1, R2, R3: 5 mA at 24 V DC |
Maximum switching current | Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC |
Isolation | Between power and control terminals |
Insulation resistance | > 1 MOhm 500 V DC for 1 minute to earth |
Noise level | 56 dB conforming to 86/188/EEC |
---|---|
Power dissipation in W | 310 W(forced convection) at 380 V, switching frequency 4 kHz 54 W(natural convection) at 380 V, switching frequency 4 kHz |
Operating position | Vertical +/- 10 degree |
Electromagnetic compatibility | Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
Pollution degree | 2 conforming to IEC 61800-5-1 |
Vibration resistance | 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 |
Shock resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
Relative humidity | 5…95 % without condensation conforming to IEC 60068-2-3 |
Ambient air temperature for operation | -15…45 °C (without derating) 45…60 °C (with derating factor) |
Operating altitude | <= 1000 m without derating 1000...4800 m with current derating 1 % per 100 m |
Environmental characteristic | Chemical pollution resistance class 3C3 conforming to IEC 60721-3-3 Dust pollution resistance class 3S3 conforming to IEC 60721-3-3 |
Standards | IEC 61800-3 Environment 2 category C3 IEC 61800-3 IEC 61800-5-1 IEC 60721-3 |
Marking | CE |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 21.5 cm |
Package 1 Width | 34.0 cm |
Package 1 Length | 58.0 cm |
Package 1 Weight | 9.48 kg |
Unit Type of Package 2 | S06 |
Number of Units in Package 2 | 3 |
Package 2 Height | 73.0 cm |
Package 2 Width | 80.0 cm |
Package 2 Length | 60.0 cm |
Package 2 Weight | 36.44 kg |